An Air System defines how air is delivered to a building's spaces. The system covers how the air is treated from outside conditions, how the air is controlled ,and what local room units are utilized. Following is a full list of the current systems options in cove.tool which covers all code baselines and more energy efficiency solutions. To see how each of these systems interacts with specific heating and cooling systems refer to the System Types article. This article will cover the following air system types:
CAV with Reheat
CAV with Radiant
VAV with Reheat
VAV with Radiant
DOAS with FCU
DOAS with VRF
DOAS with Induction
DOAS with Radiant
DOAS with WSHP
Single Zone
Natural Ventilation
Air System Types
CAV with Reheat
Constant Air Volume (CAV) systems deliver a constant amount of air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local reheat coils. CAV with Reheat systems can operate with a variety of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Ground Source Heat Pump | Air Source Heat Pump |
Water Cooled Chiller | X | X | X |
| X |
Air Cooled Chiller | X | X | X |
| X |
Ground Source Heat Pump |
|
|
| X |
|
Packaged DX | X | X | X |
| X |
CAV with Radiant
Constant Air Volume (CAV) systems deliver a constant amount of air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local radiant units, typically radiant panels or baseboard heaters. CAV with Radiant systems in cove.tool are formatted to match Canadian National Energy Code for Buildings (NECB) baseline system types. The supported options are
| Gas Boiler | Electric Resistance |
Packaged DX | X | X |
VAV with Reheat
Variable Air Volume (VAV) systems deliver a variable amount of air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local reheat coils. Air flows are turned down to minimum settings when zones do not require additional conditioning reducing energy use. VAV with Reheat systems can operate with a variety of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Ground Source Heat Pump | Air Source Heat Pump |
Water Cooled Chiller | X | X | X |
| X |
Air Cooled Chiller | X | X | X |
| X |
Ground Source Heat Pump |
|
|
| X |
|
Packaged DX | X | X | X |
| X |
VAV with Radiant
Variable Air Volume (VAV) systems deliver a variable amount of air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local radiant units, typically radiant panels or baseboard heaters. Air flows are turned down to minimum settings when zones do not require additional conditioning reducing energy use. VAV with Radiant systems in cove.tool are formatted to match Canadian National Energy Code for Buildings (NECB) baseline system types. The supported options are
| Gas Boiler | Electric Resistance |
Water Cooled Chiller | X | X |
DOAS with FCU
Dedicated Outdoor Air Systems (DOAS) deliver the minimum required ventilation air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local units, in this case, Fan Coil Units (FCU) that handle all heating and cooling loads. DOAS with FCU systems can operate with a variety of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Ground Source Heat Pump | Air Source Heat Pump |
Water Cooled Chiller | X | X | X |
| X |
Air Cooled Chiller | X | X | X |
| X |
Ground Source Heat Pump |
|
|
| X |
|
DOAS with VRF
Dedicated Outdoor Air Systems (DOAS) deliver the minimum required ventilation air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local units, in this case, Variable Refrigerant Flow Units (VRF) that handle all heating and cooling loads. DOAS with VRF systems can operate as an air source or water source system, and a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Air Source VRF |
Air Source VRF |
|
| X |
Cooling Tower | X | X |
|
DOAS with Induction
Dedicated Outdoor Air Systems (DOAS) deliver the minimum required ventilation air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local units, in this case an Induction System that handles all heating and cooling loads. Typical Induction Systems include Active Chilled Beams and induction units. DOAS with Induction systems can operate with a variety of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Ground Source Heat Pump | Air Source Heat Pump |
Water Cooled Chiller | X | X | X |
| X |
Air Cooled Chiller | X | X | X |
| X |
Ground Source Heat Pump |
|
|
| X |
|
DOAS with Radiant
Dedicated Outdoor Air Systems (DOAS) deliver the minimum required ventilation air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local units, in this case, radiant panels. Radiant cooling panels have low capacities limiting their application. DOAS with Radiant systems can operate with a variety of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Ground Source Heat Pump | Air Source Heat Pump |
Water Cooled Chiller | X | X | X |
| X |
Air Cooled Chiller | X | X | X |
| X |
Ground Source Heat Pump |
|
|
| X |
|
DOAS with WSHP
Dedicated Outdoor Air Systems (DOAS) deliver the minimum required ventilation air to all zones of a building during occupied hours from central air handling units (AHU). The temperature of each zone is controlled through local units, in this case, Water Source Heat Pumps (WSHP). The WSHP uses a condenser water loop as the source for heating and cooling in each zone. DOAS with WSHP systems operate with a few heat generation and heat rejection options, a matrix of those supported by cove.tool follows.
| Gas Boiler | Electric Boiler |
Cooling Tower | X | X |
Single Zone
A Single Zone system delivers air to a building as a whole entity. Temperature is controlled for the whole building only and there are no local zone units. Single Zone systems are typically found in residential, industrial, and retail buildings. Common applications such as packaged terminal air conditioners (PTAC) and packaged rooftop air conditioners (PSV) are modeled with the Single Zone in cove.tool. Single Zone systems can utilize a wide array of heating and cooling systems, a matrix of those supported by cove.tool follows.
| Gas Boiler | Furnace | Electric Boiler | Electric Resistance |
Water Cooled Chiller | X | X | X | X |
Air Cooled Chiller | X | X | X | X |
Packaged DX | X | X | X | X |
Direct Expansion |
| X |
|
|
Natural Ventilation
Natural Ventilation systems do not deliver any forced ventilation air to the building, instead, the ventilation is achieved passively through openings. The temperature of each zone is controlled through local units, often some form of radiant heating and direct expansion cooling. The natural ventilation systems supported by cove.tool follows.
| Gas Boiler | Electric Boiler | Electric Resistance | Air Source Heat Pump |
Direct Expansion | X | X | X | X |
Related Articles